Simgenet Teleprotection Unit

Simgenet Industrial Teleprotection Unit SMG50

Simgenet Industrial Teleprotection Unit SMG50 is a next-generation industrial teleprotection device designed for secure and fast transmission of protection relay commands on energy transmission lines, fully compliant with TEIAS-MYD/2024-062.0 specification, meeting IEC 60834-1 performance standard. Features 8 isolated inputs, 8 relay outputs, dual redundant PSU, fiber/E1/RS232 communication, 2–10 ms end-to-end transmission time.

Simgenet Industrial Teleprotection Unit SMG50

Simgenet Industrial Teleprotection Unit SMG50 is a next-generation industrial teleprotection device designed for secure, fast and reliable end-to-end transmission of protection relay commands on energy transmission lines. Developed to provide full compliance with TEIAS-MYD/2024-062.0 technical specification, it meets the IEC 60834-1 performance standard.

Core Features
  • 8 Isolated Digital Inputs + 8 Relay Digital Outputs: Directly operable in 110 V DC and 220 V DC systems. All inputs and outputs are mutually isolated. Outputs feature MOV overvoltage protection.
  • 2–10 ms End-to-End Transmission Time: The entire process including signal detection, processing, transmission and output is completed in the 2–10 ms range. Stable and repeatable time distribution.
  • Multiple Communication Interface: RS232, Fiber Optic (OPGW compatible) and E1 (ITU-T G.703) communication channels are supported. Depending on model configuration, up to 3 simultaneous communication links are possible.
  • Dual Redundant Power Supply: Two independent, galvanically isolated, active/active redundant -48 V DC power supplies. Hot-swappable design allows PSU replacement during operation.
  • Self-Monitoring: Communication failures and system failures (power/time synchronization) are separately reported through inverter-type alarm relays.
Command Acceptance and Noise Rejection

Digital inputs do not accept signals shorter than 2 ms as valid commands. This feature prevents transient noise and spurious signals occurring in industrial environments from being misinterpreted as commands. Operating range of 75–140 V DC for 110 V DC systems and 150–280 V DC for 220 V DC systems is supported.

Relay Durability and Load Conditions

Digital output relays are tested for continuous current carrying at 120% of rated voltage (110 V DC — 1 A / 220 V DC — 0.5 A), instantaneous open/close operation (≥ 0.3 A, ≥ 200 ms) and repeated open/close cycles (100/1000/5200 duty).

Time Synchronization and Event Logging

Primary and secondary time servers can be defined via SNTP protocol. Alarm is generated upon synchronization loss. The device can store at least 2000 time-stamped event records; records are preserved during power loss.

Front Panel and Monitoring

LED indicators show power, communication, time synchronization, input and output status. Input/output LEDs are latched and can be reset via reset button. Device status and event records can be monitored via LCD/LED display showing time information. Device status can be monitored and event records can be exported to a computer through the service port via web interface.

Model Configurations
  • SMG-TPU-V2-RS232: RS232 — 1 Link
  • SMG-TPU-V2-RS232-FIBER: RS232 + Fiber — 2 Link
  • SMG-TPU-V2-RS232-E1: RS232 + E1 — 2 Link
  • SMG-TPU-V2-RS232-FIBER-E1: RS232 + Fiber + E1 — 3 Link
EMC and Environmental Durability

The device has passed IEC 61000 series EMC tests (ESD 8kV/15kV, Surge 2kV, RF 10V/m, Magnetic Field 30A/m, Damped Oscillation 2.5kV) and environmental tests (-20°C cold / +60°C dry heat). IEC 60255-27 dielectric strength tests have been applied.

Use Cases
  • 154 kV / 400 kV energy transmission lines
  • Transformer station (TM) protection signaling
  • TEIAS energy transmission infrastructure
  • Energy generation and transmission facilities
  • Critical infrastructure protection communication
TEIAS Specification Compliance

Simgenet Industrial Teleprotection Unit SMG50 is designed to provide full compliance with all provisions of the TEIAS-MYD/2024-062.0 technical specification. The product is supplied with TEIAS Compliance Matrix, FAT/SAT test procedures and relay validation documentation.

General Features
Product TypeIndustrial Teleprotection Unit V2 (Protection Signaling Communication Device)
ManufacturerSimgenet Engineering — Local manufacturing
Reference SpecificationTEIAS-MYD/2024-062.0
Performance StandardIEC 60834-1
Form Factor19-inch rack-type panel compliant, metal chassis
TopraklamaExternal grounding connection on back
Communication RedundancyMultiple link support (depends on model configuration, max 3 links)
Command Input/Output
Digital Input (DI)8 independent, isolated digital command inputs
DI — 110 V DC Operating Voltage75 – 140 V DC
DI — 220 V DC Operating Voltage150 – 280 V DC
Command Accept Time> 2 ms (signals below 2 ms are not accepted as commands)
Command Reject Voltage (110V)< 66 V DC
Command Reject Voltage (220V)< 132 V DC
Digital Output (DO)8 independent, relay-based digital command outputs
Output ProtectionMOV surge protection
Input/Output IsolationAll inputs and outputs isolated from each other
Relay Features and Load Conditions
110 V DC Continuous CarryRated voltage +20%, 1 A current, 1 min continuous — 3 repetitions
220 V DC Continuous CarryRated voltage +20%, 0.5 A current, 1 min continuous — 3 repetitions
Instantaneous Open/CloseAnma gerilimi +%20, ≥ 0,3 A, minimum 200 ms
Repetitive Open/CloseStable operation at 100 / 1000 / 5200 duty cycles
Command Transfer Times
End-to-End Signal Transmission Time2 – 10 ms (including detection + processing + transmission + output)
Hassasiyet< 2 ms precision measurement
Time DistributionStable and repeatable
Communication Interfaces
RS232RS232 seri communication portu
Fiber OptikSM fiber support (OPGW compliant)
E1 (G.703)ITU-T G.703 digital transmission interface
Available Model Configurations
SMG-TPU-V2-RS232RS232 — 1 Link
SMG-TPU-V2-RS232-FIBERRS232 + Fiber — 2 Link
SMG-TPU-V2-RS232-E1RS232 + E1 — 2 Link
SMG-TPU-V2-RS232-FIBER-E1RS232 + Fiber + E1 — 3 Link
Front Panel and Indicators
LED IndicatorsPower, communication, time synchronization, input and output states
Input/Output LEDSealed (latch) — LED reset button with resettable
EkranLCD/LED screen — time information and event logs viewable
Control ButtonsAt least 3 control buttons
Time Synchronization and Event Logging
Time SynchronizationSNTP protocol (primary and secondary servers configurable)
Sync Loss AlarmAlarm generation when SNTP connection is lost
Event Logging≥ 2000 time-stamped event records
Log ProtectionRecords not deleted when power is lost
Log ManagementFIFO — oldest record deleted when memory is full
Alarm Outputs
Communication AlarmCommunication link failure — inverter contact alarm relay
System AlarmPower supply or time synchronization failure — inverter contact alarm relay
Kendi Kendini DenetlemeSupported
Servis Portu and Management
Servis PortuDevice status monitoring via web interface
Event ExportEvent records can be exported to computer
Power and Environmental Conditions
Power Supply-48 V DC (operating range: -42 V DC … -68 V DC)
PSU StructureDual independent, galvanically isolated, active/active redundant power supply
PSU TypeSlide-mounted, plug-and-play (hot-swap) — exchange supported during operation
Operating Temperature-20°C ~ +60°C
EMC and Security Certifications
ESD (IEC 61000-4-2)8 kV temas / 15 kV hava
RF Immunity (IEC 61000-4-3)10 V/m
EFT/Burst (IEC 61000-4-4)Level 3
Surge (IEC 61000-4-5)2 kV
Conducted RF (IEC 61000-4-6)10 V
Magnetic Field (IEC 61000-4-8)30 A/m
Damped Oscillation (IEC 61000-4-18)2,5 kV
Emisyon (IEC 61000-6-4 / EN 55032)Industrial limits
Cold Test (IEC 60068-2-1)-20°C / 2 saat
Dry Heat Test (IEC 60068-2-2)+60°C / 2 saat
Dielectric Strength (IEC 60255-27)0,5 kV / 2 kV — 1 dk
Positioning
Application Area154 kV / 400 kV energy transmission lines — transformer station protection signaling
Target SectorTEIAS, energy generation and transmission facilities, critical infrastructure
Specification ComplianceFull compliance with TEIAS-MYD/2024-062.0 technical specification

For detailed technical information, please refer to the product user manual and test documents.